FDMR fire dampers are designed to prevent fire and reduce the spread of smoke through ventilation ducts penetrating fire-rated walls or floors between fire compartments.
Product code | 511732 |
---|---|
HVAC number | 8433005 |
Package size | 1 |
Product code | 511734 |
---|---|
HVAC number | 8433006 |
Package size | 1 |
Product code | 511730 |
---|---|
HVAC number | 8433004 |
Package size | 1 |
Product code | 511736 |
---|---|
HVAC number | 8433007 |
Package size | 1 |
FDMR fire dampers are designed to prevent fire and reduce the spread of smoke through ventilation ducts penetrating fire-rated walls or floors between fire compartments.
Fire dampers Ø 100-800 mm
CE marked according to standard EN 15650
Tested according to standard EN 1366-2
Fire classification according to standard EN 13501-3+A1
Fire resistance EIS 120
Frame tightness class C, damper tightness class 3 according to standard EN 1751
Corrosion resistance according to standard EN 15650
Classified C10000 (open/close cycle test) according to standard EN 15650
Fire dampers are available in manual and motorized versions
Maximum air velocity in the open damper is 12 m/s and maximum pressure difference is 1200 Pa
Usage unit | pcs |
---|